Measuring heat-pipe quality
This page describes test procedures, measurements and results from comparing heat transfer capabilities between a certain type of heat-pipes.
Test method
| | |
Testing four heat-pipe | Clamp with transistor | Temperature measurement |
Results
Compaq nx6110 nc6110 nx6120 nc6120 heat-pipe measurements |
|
Conclusion
Heat-pipe #0 is clearly broken. Because the heat-pipe is not transferring any heat away, the temperature rises locally substantially, this can be seen in the graph. Further measurements at this heat-pipe had to be stopped to prevent damage to the transistor
Heat-pipe #3 performs the best. At a room temperature of 22.1 °C, the final temperature when no further rise or fall can be detected is 35.9 °C. The dissipated power had been set to 18.5W